Pump controller
TOSCANO
Vigilec DRAIN Control V2DC
Pump controller for wastewater and stormwater.
- Unit for waste & sewage stations, control and protection of 2 pumps (up to 7.5 CV 400 V) with automatic alternation. Control through 2, 3 or 4 floats or level switches.
- Three-phase or single-phase.
- Dual voltage supply 230/400 VAC.
- Phase failure protection.
- Protection against failure in wiring to pump.
- Over-voltage protection.
- Overload protection.
- Protection against dry running through floats.
- Guaranteed against connection failures.
- Protection against jammed impeller during long resting periods. Unit activates motor for one second every 24 hours (only in AUTO mode).
- Assured operation on failure in any float.
- Assured operation of first pump on failure of the second one.
- Second pump delay (re-starting due to supply cut).
- Electronic overload relay, scalable (for each pump).
- Audible high level alarm (90dB).
- Operation selection (simultaneus or delayed shutdown).
- Control elements are low voltage.
- Load break safety switch.
- Calibrated fuse switch.
- Power contactors.
- Pilot lights for VOLTAGE and HIGH LEVEL.
- Pilot for ON/OFF and OVERLOAD for each pump.
- Overload alarm reset button.
- Wide diameter range and high protection in cable glands.
- Option: magnetic circuit breaker.
- Adjustable temporisation of motor shutdown.
- Six alarm outputs: General alarm, High level, Motor 1 running, Pump 2 running, Pump 1 overload, Pump 2 overload.
- General alarm output at 230 VAC (on request).
- Auxiliary inputs for thermal probes (klixon).
- MAN-O-AUTO buttons per pump.
- Includes batteries for high level alarm in case of supply cut.
- Correct sense turn indication light (three-phase motors).
Ask for enquiry